Five of the 59 questions in this pack
A 5kW (power consumption) server keeps crashing with the message ‘temperature too high’. - The intake temperature is measured at 25 °C/77 °F and a relative humidity (RH) level of 50%. - The exhaust temperature is 29 °C/84 °F and 45% RH. - The raised floor is providing adequate amount of CFM/CMH at a reasonable velocity. - The pressure under the raised floor is approximately 25 Pa/0.1 inch H20. Analyze the situation and indicate what the most likely cause is for this server to crash.
- A. Dust inside the server causing issues with convection-based heat transfer
- B. The exhaust temperature is exceeding the ASHRAE recommended values
- C. The raised floor pressure is too low and/or the raised floor tile % opening is not adequate
- D. No cause could be determined as the CFM/CMH of the air conditioning equipment is not stated
Show answer and explanation
Correct answer: A. Dust inside the server causing issues with convection-based heat transfer
The air reaching the server is within normal limits and the floor supply is described as adequate, so the cause must lie inside the server. Dust that blocks heat transfer from the components to the passing air fits a server that overheats despite good intake air.
Why the other options are wrong
- B. ASHRAE recommended values apply to the air at the server intake, and the intake here is fine.
- C. The scenario states that the raised floor delivers adequate airflow at a reasonable velocity.
- D. The scenario already says the airflow is adequate, so a cause can be determined.
What is the main disadvantage of using a ToR (Top of Rack) design?
- A. A single ToR (Top of Rack) switch is more expensive than an EoR (End of Row) switch.
- B. You need a separate rack to install all your ToR (Top of Rack) switches.
- C. There will be more switches to manage.
- D. A ToR (Top of Rack) switch has only optical interfaces.
Show answer and explanation
Correct answer: C. There will be more switches to manage.
A Top of Rack design puts a switch in every rack, so a row needs many more switches than an End of Row design with a shared switch. Each one has to be managed, patched and updated.
Why the other options are wrong
- A. The cost of a single switch is not the main drawback of the design.
- B. ToR switches sit in the racks they serve, so no separate rack is needed.
- D. ToR switches offer copper ports as well as optical ones.
The location of a data center is just above the Arctic Circle (North Pole). The outside air temperature is never above 21 °C/70 °F. Taking energy efficiency as the highest priority, which cooling system should you recommend?
- A. Standard air conditioning units, as spares might be not readily available
- B. Any cooling system can be efficient, because the outside air temperature will not influence the temperature of the air intake of the ICT equipment
- C. Waterside economizer
- D. Airside economizer
Show answer and explanation
Correct answer: D. Airside economizer
When outside air is always cool enough, an airside economizer can bring it into the room directly and avoid running compressors, which is the most efficient option.
Why the other options are wrong
- A. Standard air conditioning wastes energy when free cooling is available all year.
- B. Outside air temperature does matter when outside air is used for cooling.
- C. A waterside economizer can use cold conditions too, but it adds a heat exchange step, so it is less efficient than using the cool outside air directly.
When are the wet bulb’s and dry bulb’s temperature identical?
- A. When the dry bulb’s temperature is at the lowest allowable temperature for IT equipment as per the ASHRAE
- B. When the dry bulb’s temperature is at the highest allowable temperature for IT equipment as per the ASHRAE
- C. When the relative humidity is at the best practice value for relative humidity, being 50% RH
- D. When the relative humidity is 100%
Show answer and explanation
Correct answer: D. When the relative humidity is 100%
The wet bulb reads lower than the dry bulb because evaporation cools it. At 100% relative humidity the air cannot take up more moisture, so no cooling happens and both readings are the same.
Why the other options are wrong
- A. The two readings depend on humidity, not on the ASHRAE temperature limits.
- B. The ASHRAE limit does not make the two readings equal.
- C. At 50% RH evaporation still occurs, so the wet bulb is lower than the dry bulb.
An air-conditioner unit needs to be selected. Two types are available: - Unit-A has a Sensible Heat Ratio (SHR) of 0.7. - Unit-B has a Sensible Heat Ratio (SHR) of 0.9. From an efficiency point of view, which one should be selected?
- A. It does not matter, as the Sensible Heat Ratio has nothing to do with efficiency.
- B. Not relevant, as Sensible Heat Ratio is only specified for air-conditioner equipment to indicate the ratio between intake temperature and exhaust temperature.
- C. Unit A
- D. Unit B
Show answer and explanation
Correct answer: D. Unit B
IT equipment gives off almost only sensible heat. A unit with a higher SHR puts more of its capacity into lowering air temperature and less into removing moisture, so Unit B wastes less energy.
Why the other options are wrong
- A. SHR describes how much of the cooling capacity is sensible cooling, so it does affect efficiency.
- B. SHR is a ratio of sensible to total cooling, not a ratio of intake to exhaust temperature.
- C. Unit A spends more of its capacity on dehumidifying, which the data hall does not need.
Try EXIN CDCS free first
59 questions in the full pack- Free sample: 23 questions 23 real questions, every answer explained, in one PDF. Download PDF
- Full pack, $39.00 USD paid once All 59 questions, every answer explained, plus a questions-only PDF. Updates for life.Get the full pack
CDCS exam questions with answers: all 59 for the EXIN EPI Certified Data Centre Specialist exam.
This pack is the complete set, covering every part of the CDCS course syllabus. Download the free sample to see the question style first.
- 59 exam practice questions: mapped to the CDCS course syllabus
- Complete answers and explanations, including why every wrong option is wrong
- Questions-only PDF: for timed practice
- Email delivery: sent to your email within 24 hours
- Free monthly updates for life
You pay for this PDF once, with a refund if you fail anyway.
CDCS exam questions: the short answers
How many questions are on the CDCS exam?
EXIN lists 60 multiple-choice questions and 1 hour 30 minutes. The exam is closed book, and a calculator that is not a smartphone is allowed.
What is the pass mark?
The pass mark is 75%.
Do I need anything before the CDCS exam?
Yes. EXIN requires a valid Certified Data Centre Professional (CDCP) certificate, and training is mandatory.
What makes this exam hard
The exam rewards numbers and design judgment, not definitions. EXIN lists three main subjects: the data centre life cycle and standards, designing and implementing a data centre, and environmental considerations and efficiency. Questions give you a scenario with temperatures, airflow or power figures and ask which design choice or fault explains it.
Cooling is a recurring theme in the course syllabus: CFM, Delta-T, humidity, economizers and efficiency measures. Learn the figures and relationships well enough to apply them, because a calculator is allowed and the answers often come from a short calculation.
Before you buy
Free questions
Real EXIN CDCS questions are free on the site, each with the answer explained.
What you get for $39.00 USD
- All 59 questions, each with the correct answer and why the other options are wrong
- 2 PDFs: the full pack, plus a questions-only copy for timed practice
- Delivered to your email within 24 hours
- Updated once a month, with free updates for life, emailed to the address you used at checkout
- Paid once
What do I get?
Every pack comes as 2 PDFs: one with every answer explained, and a questions-only copy for timed practice. This pack is delivered to your email within 24 hours, and every pack includes free updates for life.
How often are the questions updated?
Question sets are updated once a month. The date of the latest update is shown on every exam page.
Will I receive updates after purchasing?
Yes. All PDF purchases include lifetime updates. Updated versions are emailed automatically to the email address used during checkout.
What if an answer looks wrong?
We correct mistakes as we find them, and the monthly update sends those fixes to you. No question bank this size is ever completely flawless, so if something still looks off to you, check it against the vendor's own documentation and send it to support@dailydebian.com. We reply to every message, and the fix ships in the next update, free, for life.
Are your materials enough to pass the exam?
Most candidates use them as their main practice source. If you study with them and still fail, we refund you in full.
What happens if I fail my exam?
You get your money back. Email support@dailydebian.com within 14 days of receiving your results, with your order number and a copy of your official score report showing the fail. Requests are reviewed within 5 to 7 business days and approved refunds go back to the original payment method. Full terms are in the refund policy.
Do you have discount codes?
Yes, when you buy more than one exam pack. For 2 packs, use code BUY2 for 15% off. For 3 or more packs, use code BUY3 for 20% off. Enter the code in the discount box at checkout.
What payment methods do you accept?
Visa, Mastercard, American Express, UnionPay, Apple Pay, Google Pay, Shop Pay and PayPal. All prices are shown in your local currency at checkout.
Do you offer shipping?
No. All products are digital downloads. There is no physical shipping.
I did not receive my order after payment.
Contact support@dailydebian.com with your order number and payment confirmation details.